Filtered by vendor Schneider-electric
Subscribe
Total
758 CVE
| CVE | Vendors | Products | Updated | CVSS v2 | CVSS v3 |
|---|---|---|---|---|---|
| CVE-2016-4520 | 1 Schneider-electric | 1 Pelco Digital Sentry Video Management System Firmware | 2025-04-12 | 10.0 HIGH | 9.8 CRITICAL |
| Schneider Electric Pelco Digital Sentry Video Management System with firmware before 7.14 has hardcoded credentials, which allows remote attackers to obtain access, and consequently execute arbitrary code, via unspecified vectors. | |||||
| CVE-2015-8561 | 1 Schneider-electric | 1 Proclima | 2025-04-12 | 6.8 MEDIUM | N/A |
| The F1BookView ActiveX control in F1 Bookview in Schneider Electric ProClima before 6.2 allows remote attackers to execute arbitrary code or cause a denial of service (memory corruption) via a crafted integer value to the (1) AttachToSS, (2) CopyAll, (3) CopyRange, (4) CopyRangeEx, or (5) SwapTable method, a different vulnerability than CVE-2015-7918. | |||||
| CVE-2015-0982 | 1 Schneider-electric | 1 Pelco Ds-nv | 2025-04-12 | 7.5 HIGH | N/A |
| Buffer overflow in an unspecified DLL in Schneider Electric Pelco DS-NVs before 7.8.90 allows remote attackers to execute arbitrary code via unspecified vectors. | |||||
| CVE-2015-7918 | 1 Schneider-electric | 1 Proclima | 2025-04-12 | 6.8 MEDIUM | N/A |
| Multiple buffer overflows in the F1BookView ActiveX control in F1 Bookview in Schneider Electric ProClima before 6.2 allow remote attackers to execute arbitrary code via the (1) Attach, (2) DefinedName, (3) DefinedNameLocal, (4) ODBCPrepareEx, (5) ObjCreatePolygon, (6) SetTabbedTextEx, or (7) SetValidationRule method, a different vulnerability than CVE-2015-8561. | |||||
| CVE-2016-2292 | 1 Schneider-electric | 4 Proface Gp-pro Ex Ex-ed, Proface Gp-pro Ex Pfxexedls, Proface Gp-pro Ex Pfxexedv and 1 more | 2025-04-12 | 4.3 MEDIUM | 6.5 MEDIUM |
| Stack-based buffer overflow in Pro-face GP-Pro EX EX-ED before 4.05.000, PFXEXEDV before 4.05.000, PFXEXEDLS before 4.05.000, and PFXEXGRPLS before 4.05.000 allows remote attackers to execute arbitrary code via unspecified vectors. | |||||
| CVE-2016-2278 | 1 Schneider-electric | 4 Struxureware Building Operations Automation Server As, Struxureware Building Operations Automation Server As-p, Struxureware Building Operations Automation Server As-p Firmware and 1 more | 2025-04-12 | 9.0 HIGH | 7.2 HIGH |
| Schneider Electric Struxureware Building Operations Automation Server AS 1.7 and earlier and AS-P 1.7 and earlier allows remote authenticated administrators to execute arbitrary OS commands by defeating an msh (aka Minimal Shell) protection mechanism. | |||||
| CVE-2016-2291 | 1 Schneider-electric | 4 Proface Gp-pro Ex Ex-ed, Proface Gp-pro Ex Pfxexedls, Proface Gp-pro Ex Pfxexedv and 1 more | 2025-04-12 | 4.3 MEDIUM | 6.5 MEDIUM |
| Pro-face GP-Pro EX EX-ED before 4.05.000, PFXEXEDV before 4.05.000, PFXEXEDLS before 4.05.000, and PFXEXGRPLS before 4.05.000 allow remote attackers to execute arbitrary code or cause a denial of service (out-of-bounds read) via unspecified vectors. | |||||
| CVE-2014-8511 | 1 Schneider-electric | 1 Proclima | 2025-04-12 | 10.0 HIGH | N/A |
| Buffer overflow in an ActiveX control in Atx45.ocx in Schneider Electric ProClima before 6.1.7 allows remote attackers to execute arbitrary code via unspecified vectors, a different vulnerability than CVE-2014-8512. NOTE: this may be clarified later based on details provided by researchers. | |||||
| CVE-2015-3962 | 1 Schneider-electric | 1 Struxureware Building Expert Multi-purpose Management | 2025-04-12 | 5.0 MEDIUM | N/A |
| Schneider Electric StruxureWare Building Expert MPM before 2.15 does not use encryption for the client-server data stream, which allows remote attackers to discover credentials by sniffing the network. | |||||
| CVE-2013-2761 | 1 Schneider-electric | 1 Modicon M340 | 2025-04-11 | 4.0 MEDIUM | N/A |
| The Schneider Electric M340 BMXNOE01xx and BMXP3420xx PLC modules allow remote authenticated users to cause a denial of service (module crash) via crafted FTP traffic, as demonstrated by the FileZilla FTP client. | |||||
| CVE-2011-4036 | 1 Schneider-electric | 3 Citecthistorian, Citectscada Reports, Vijeo Historian | 2025-04-11 | 5.0 MEDIUM | N/A |
| Directory traversal vulnerability in Schneider Electric Vijeo Historian 4.30 and earlier, CitectHistorian 4.30 and earlier, and CitectSCADAReports 4.10 and earlier allows remote attackers to read arbitrary files via unspecified vectors. | |||||
| CVE-2013-0687 | 1 Schneider-electric | 1 Micom S1 Studio | 2025-04-11 | 6.6 MEDIUM | N/A |
| The installer routine in Schneider Electric MiCOM S1 Studio uses world-writable permissions for executable files, which allows local users to modify the service or the configuration files, and consequently gain privileges or trigger incorrect protective-relay operation, via a Trojan horse executable file. | |||||
| CVE-2011-4860 | 1 Schneider-electric | 3 Quantum Ethernet Module 140noe77100, Quantum Ethernet Module 140noe77101, Quantum Ethernet Module 140noe77111 | 2025-04-11 | 10.0 HIGH | N/A |
| The ComputePassword function in the Schneider Electric Quantum Ethernet Module on the NOE 771 device (aka the Quantum 140NOE771* module) generates the password for the fwupgrade account by performing a calculation on the MAC address, which makes it easier for remote attackers to obtain access via a (1) ARP request message or (2) Neighbor Solicitation message. | |||||
| CVE-2013-0664 | 1 Schneider-electric | 3 Modicon M340, Modicon Premium, Modicon Quantum Plc | 2025-04-11 | 8.5 HIGH | N/A |
| The FactoryCast service on the Schneider Electric Quantum 140NOE77111 and 140NWM10000, M340 BMXNOE0110x, and Premium TSXETY5103 PLC modules allows remote authenticated users to send Modbus messages, and consequently execute arbitrary code, by embedding these messages in SOAP HTTP POST requests. | |||||
| CVE-2011-5163 | 2 Mitsubishi-automation, Schneider-electric | 2 Mx4 Scada, Citectscada | 2025-04-11 | 4.6 MEDIUM | N/A |
| Buffer overflow in an unspecified third-party component in the Batch module for Schneider Electric CitectSCADA before 7.20 and Mitsubishi MX4 SCADA before 7.20 allows local users to execute arbitrary code via a long string in a login sequence. | |||||
| CVE-2012-0929 | 1 Schneider-electric | 1 Modicon Quantum Plc | 2025-04-11 | 7.8 HIGH | 7.5 HIGH |
| Multiple buffer overflows in Schneider Electric Modicon Quantum PLC allow remote attackers to cause a denial of service via malformed requests to the (1) FTP server or (2) HTTP server. | |||||
| CVE-2011-3143 | 2 Aveva, Schneider-electric | 3 Clearscada, Scx 67, Scx 68 | 2025-04-11 | 10.0 HIGH | N/A |
| Use-after-free vulnerability in Control Microsystems ClearSCADA 2005, 2007, and 2009 before R2.3 and R1.4, as used in SCX before 67 R4.5 and 68 R3.9, allows remote attackers to cause a denial of service (crash) and possibly execute arbitrary code via unspecified long strings that trigger heap memory corruption. | |||||
| CVE-2011-4861 | 1 Schneider-electric | 3 Quantum Ethernet Module 140noe77100, Quantum Ethernet Module 140noe77101, Quantum Ethernet Module 140noe77111 | 2025-04-11 | 10.0 HIGH | N/A |
| The modbus_125_handler function in the Schneider Electric Quantum Ethernet Module on the NOE 771 device (aka the Quantum 140NOE771* module) allows remote attackers to install arbitrary firmware updates via a MODBUS 125 function code to TCP port 502. | |||||
| CVE-2013-2763 | 1 Schneider-electric | 24 Modicon M340 Bmx Noc 0401, Modicon M340 Bmx Noc 0401 Firmware, Modicon M340 Bmx Noe 0100 and 21 more | 2025-04-11 | 5.0 MEDIUM | N/A |
| The Schneider Electric M340 PLC modules allow remote attackers to cause a denial of service (resource consumption) via unspecified vectors. NOTE: the vendor reportedly disputes this issue because it "could not be duplicated" and "an attacker could not remotely exploit this observed behavior to deny PLC control functions. | |||||
| CVE-2011-4033 | 1 Schneider-electric | 3 Citecthistorian, Citectscada Reports, Vijeo Historian | 2025-04-11 | 4.3 MEDIUM | N/A |
| Buffer overflow in the Steema TeeChart ActiveX control, as used in Schneider Electric Vijeo Historian 4.30 and earlier, CitectHistorian 4.30 and earlier, and CitectSCADAReports 4.10 and earlier, allows remote attackers to cause a denial of service via unspecified vectors. | |||||